ConduitCount

How many #1/0 THHN fit in 3" IMC?

171/0 AWG THHN/THWN-2 wires in 3" Intermediate metal conduit

7.922 sq in × 40 % = 3.1688 sq in allowed. ÷ 0.1855 sq in per wire = 17.08, so 17.

17 #1/0 THHN in 3" IMC, drawn to scale

This pull in numbers

17 wires fill
39.8 % of 3" IMC
Limit for three or more
40 %
For 18 or more
3-1/2" IMC, up to 23
Pipe to wire diameter
6.53 to 1
In THW insulation
14 fit
In XHHW-2 insulation
17 fit

Before you pull 17

#1/0 THHN in other 3" conduit

#1/0 THHN in other IMC sizes

Other wire sizes in 3" IMC