ConduitCount

How many #1 THHN fit in 2" EMT?

81 AWG THHN/THWN-2 wires in 2" Electrical metallic tubing

3.356 sq in × 40 % = 1.3424 sq in allowed. ÷ 0.1562 sq in per wire = 8.59, so 8.

8 #1 THHN in 2" EMT, drawn to scale

This pull in numbers

8 wires fill
37.2 % of 2" EMT
Limit for three or more
40 %
For 9 or more
2-1/2" EMT, up to 15
Pipe to wire diameter
4.63 to 1
In THW insulation
7 fit
In XHHW-2 insulation
8 fit

Before you pull 8

#1 THHN in other 2" conduit

#1 THHN in other EMT sizes

Other wire sizes in 2" EMT

Charts