ConduitCount

How many #1 THHN fit in 2" Rigid?

81 AWG THHN/THWN-2 wires in 2" Rigid metal conduit (RMC, GRC)

3.408 sq in × 40 % = 1.3632 sq in allowed. ÷ 0.1562 sq in per wire = 8.73, so 8.

8 #1 THHN in 2" Rigid, drawn to scale

This pull in numbers

8 wires fill
36.7 % of 2" Rigid
Limit for three or more
40 %
For 9 or more
2-1/2" Rigid, up to 12
Pipe to wire diameter
4.67 to 1
In THW insulation
7 fit
In XHHW-2 insulation
9 fit

Before you pull 8

#1 THHN in other 2" conduit

#1 THHN in other Rigid sizes

Other wire sizes in 2" Rigid

Charts