ConduitCount

How many #1 THHN fit in 2" IMC?

91 AWG THHN/THWN-2 wires in 2" Intermediate metal conduit

3.630 sq in × 40 % = 1.4520 sq in allowed. ÷ 0.1562 sq in per wire = 9.30, so 9.

9 #1 THHN in 2" IMC, drawn to scale

This pull in numbers

9 wires fill
38.7 % of 2" IMC
Limit for three or more
40 %
For 10 or more
2-1/2" IMC, up to 13
Pipe to wire diameter
4.82 to 1
In THW insulation
7 fit
In XHHW-2 insulation
9 fit

Before you pull 9

#1 THHN in other 2" conduit

#1 THHN in other IMC sizes

Other wire sizes in 2" IMC

Charts