251 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 40

9.737 sq in × 40 % = 3.8948 sq in allowed. ÷ 0.1562 sq in per wire = 24.93, which Note 7 rounds up to 25 because the decimal is 0.8 or more.

25 #1 THHN in 3-1/2" PVC Sch 40, drawn to scale

This pull in numbers

25 wires fill
40.1 % of 3-1/2" PVC Sch 40
Limit for three or more
40 %
For 26 or more
4" PVC Sch 40, up to 32
Pipe to wire diameter
7.89 to 1
In THW insulation
20 fit
In XHHW-2 insulation
25 fit

Before you pull 25

#1 THHN in other 3-1/2" conduit

#1 THHN in other PVC Sch 40 sizes

Other wire sizes in 3-1/2" PVC Sch 40