ConduitCount

How many #10 THHN fit in 3-1/2" PVC Sch 80?

16410 AWG THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 80

8.688 sq in × 40 % = 3.4752 sq in allowed. ÷ 0.0211 sq in per wire = 164.70, so 164.

164 #10 THHN in 3-1/2" PVC Sch 80, drawn to scale

This pull in numbers

164 wires fill
39.8 % of 3-1/2" PVC Sch 80
Limit for three or more
40 %
For 165 or more
4" PVC Sch 80, up to 213
Pipe to wire diameter
20.28 to 1
In THW insulation
143 fit
In XHHW-2 insulation
143 fit

Before you pull 164

#10 THHN in other 3-1/2" conduit

ConduitInside areaMost #10 THHN
Electrical metallic tubing11.545219
Intermediate metal conduit10.584200
Rigid metal conduit (RMC, GRC)10.010189
Rigid PVC conduit, Schedule 409.737184
Rigid PVC conduit, Schedule 808.688164
Flexible metal conduit (FMC, Greenfield)9.621182
Liquidtight flexible metal conduit (LFMC)9.731184

#10 THHN in other PVC Sch 80 sizes

Other wire sizes in 3-1/2" PVC Sch 80

Charts