ConduitCount

How many #12 THHN fit in 1-1/2" IMC?

6712 AWG THHN/THWN-2 wires in 1-1/2" Intermediate metal conduit

2.225 sq in × 40 % = 0.8900 sq in allowed. ÷ 0.0133 sq in per wire = 66.92, which Note 7 rounds up to 67 because the decimal is 0.8 or more.

67 #12 THHN in 1-1/2" IMC, drawn to scale

This pull in numbers

67 wires fill
40.0 % of 1-1/2" IMC
Limit for three or more
40 %
For 68 or more
2" IMC, up to 109
Pipe to wire diameter
12.95 to 1
In THW insulation
49 fit
In XHHW-2 insulation
49 fit

Before you pull 67

#12 THHN in other 1-1/2" conduit

#12 THHN in other IMC sizes

Other wire sizes in 1-1/2" IMC

Charts