ConduitCount

How many #1 THHN fit in 1/2" IMC?

11 AWG THHN/THWN-2 wires in 1/2" Intermediate metal conduit

0.342 sq in × 53 % = 0.1813 sq in allowed. ÷ 0.1562 sq in per wire = 1.16.

1 #1 THHN in 1/2" IMC, drawn to scale

This pull in numbers

1 wires fill
45.7 % of 1/2" IMC
Limit for one
53 %
For 2 or more
1-1/4" IMC, up to 4
Pipe to wire diameter
1.48 to 1
In THW insulation
0 fit
In XHHW-2 insulation
1 fit

Before you pull 1

#1 THHN in other 1/2" conduit

ConduitInside areaMost #1 THHN
Electrical metallic tubing0.3041
Intermediate metal conduit0.3421
Rigid metal conduit (RMC, GRC)0.3141
Rigid PVC conduit, Schedule 400.2850
Rigid PVC conduit, Schedule 800.2170
Flexible metal conduit (FMC, Greenfield)0.3171
Liquidtight flexible metal conduit (LFMC)0.3141
Electrical nonmetallic tubing (smurf tube)0.2850

#1 THHN in other IMC sizes

Other wire sizes in 1/2" IMC

Charts