ConduitCount

How many #14 THHN fit in 1-1/2" PVC Sch 80?

7014 AWG THHN/THWN-2 wires in 1-1/2" Rigid PVC conduit, Schedule 80

1.711 sq in × 40 % = 0.6844 sq in allowed. ÷ 0.0097 sq in per wire = 70.56, so 70.

70 #14 THHN in 1-1/2" PVC Sch 80, drawn to scale

This pull in numbers

70 wires fill
39.7 % of 1-1/2" PVC Sch 80
Limit for three or more
40 %
For 71 or more
2" PVC Sch 80, up to 118
Pipe to wire diameter
13.30 to 1
In THW insulation
49 fit
In XHHW-2 insulation
49 fit

Before you pull 70

#14 THHN in other 1-1/2" conduit

#14 THHN in other PVC Sch 80 sizes

Other wire sizes in 1-1/2" PVC Sch 80

Charts