ConduitCount

How many #14 THHN fit in 2-1/2" PVC Sch 80?

17014 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 80

4.119 sq in × 40 % = 1.6476 sq in allowed. ÷ 0.0097 sq in per wire = 169.86, which Note 7 rounds up to 170 because the decimal is 0.8 or more.

170 #14 THHN in 2-1/2" PVC Sch 80, drawn to scale

This pull in numbers

170 wires fill
40.0 % of 2-1/2" PVC Sch 80
Limit for three or more
40 %
For 171 or more
3" PVC Sch 80, up to 265
Pipe to wire diameter
20.63 to 1
In THW insulation
118 fit
In XHHW-2 insulation
118 fit

Before you pull 170

#14 THHN in other 2-1/2" conduit

ConduitInside areaMost #14 THHN
Electrical metallic tubing5.858241
Intermediate metal conduit5.135211
Rigid metal conduit (RMC, GRC)4.866200
Rigid PVC conduit, Schedule 404.695193
Rigid PVC conduit, Schedule 804.119170
Flexible metal conduit (FMC, Greenfield)4.909202
Liquidtight flexible metal conduit (LFMC)4.881201

#14 THHN in other PVC Sch 80 sizes

Other wire sizes in 2-1/2" PVC Sch 80

Charts