13514 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 40

3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.0097 sq in per wire = 135.71, so 135.

135 #14 THHN in 2" PVC Sch 40, drawn to scale

This pull in numbers

135 wires fill
39.8 % of 2" PVC Sch 40
Limit for three or more
40 %
For 136 or more
2-1/2" PVC Sch 40, up to 193
Pipe to wire diameter
18.44 to 1
In THW insulation
94 fit
In XHHW-2 insulation
94 fit

Before you pull 135

#14 THHN in other 2" conduit

#14 THHN in other PVC Sch 40 sizes

Other wire sizes in 2" PVC Sch 40