ConduitCount

How many #2/0 THHN fit in 2" PVC Sch 40?

62/0 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 40

3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.2223 sq in per wire = 5.92, which Note 7 rounds up to 6 because the decimal is 0.8 or more.

6 #2/0 THHN in 2" PVC Sch 40, drawn to scale

This pull in numbers

6 wires fill
40.5 % of 2" PVC Sch 40
Limit for three or more
40 %
For 7 or more
2-1/2" PVC Sch 40, up to 8
Pipe to wire diameter
3.85 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit

Before you pull 6

#2/0 THHN in other 2" conduit

#2/0 THHN in other PVC Sch 40 sizes

Other wire sizes in 2" PVC Sch 40

Charts