How many 300 kcmil THHN fit in 2" PVC Sch 40?

3300 kcmil THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 40

3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.4608 sq in per wire = 2.86, which Note 7 rounds up to 3 because the decimal is 0.8 or more.

3 300 kcmil THHN in 2" PVC Sch 40, drawn to scale

This pull in numbers

3 wires fill
42.0 % of 2" PVC Sch 40
Limit for three or more
40 %
For 4 or more
2-1/2" PVC Sch 40, up to 4
Pipe to wire diameter
2.67 to 1
In THW insulation
1 fit
In XHHW-2 insulation
3 fit

Before you pull 3

300 kcmil THHN in other 2" conduit

300 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 2" PVC Sch 40