ConduitCount

How many #2 THHN fit in 2" PVC Sch 40?

112 AWG THHN/THWN-2 wires in 2" Rigid PVC conduit, Schedule 40

3.291 sq in × 40 % = 1.3164 sq in allowed. ÷ 0.1158 sq in per wire = 11.37, so 11.

11 #2 THHN in 2" PVC Sch 40, drawn to scale

This pull in numbers

11 wires fill
38.7 % of 2" PVC Sch 40
Limit for three or more
40 %
For 12 or more
2-1/2" PVC Sch 40, up to 16
Pipe to wire diameter
5.33 to 1
In THW insulation
10 fit
In XHHW-2 insulation
11 fit

Before you pull 11

#2 THHN in other 2" conduit

#2 THHN in other PVC Sch 40 sizes

Other wire sizes in 2" PVC Sch 40

Charts