ConduitCount

How many #2 THHN fit in 3-1/2" EMT?

402 AWG THHN/THWN-2 wires in 3-1/2" Electrical metallic tubing

11.545 sq in × 40 % = 4.6180 sq in allowed. ÷ 0.1158 sq in per wire = 39.88, which Note 7 rounds up to 40 because the decimal is 0.8 or more.

40 #2 THHN in 3-1/2" EMT, drawn to scale

This pull in numbers

40 wires fill
40.1 % of 3-1/2" EMT
Limit for three or more
40 %
For 41 or more
4" EMT, up to 51
Pipe to wire diameter
9.98 to 1
In THW insulation
34 fit
In XHHW-2 insulation
40 fit

Before you pull 40

#2 THHN in other 3-1/2" conduit

#2 THHN in other EMT sizes

Other wire sizes in 3-1/2" EMT

Charts