How many #2 THHN fit in 1-1/2" EMT?

72 AWG THHN/THWN-2 wires in 1-1/2" Electrical metallic tubing

2.036 sq in × 40 % = 0.8144 sq in allowed. ÷ 0.1158 sq in per wire = 7.03, so 7.

7 #2 THHN in 1-1/2" EMT, drawn to scale

This pull in numbers

7 wires fill
39.8 % of 1-1/2" EMT
Limit for three or more
40 %
For 8 or more
2" EMT, up to 11
Pipe to wire diameter
4.19 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit