ConduitCount

How many 250 kcmil THHN fit in 1-1/2" Rigid?

1250 kcmil THHN/THWN-2 wires in 1-1/2" Rigid metal conduit (RMC, GRC)

2.071 sq in × 53 % = 1.0976 sq in allowed. ÷ 0.3970 sq in per wire = 2.76.

1 250 kcmil THHN in 1-1/2" Rigid, drawn to scale

This pull in numbers

1 wires fill
19.2 % of 1-1/2" Rigid
Limit for one
53 %
For 2 or more
2" Rigid, up to 3
Pipe to wire diameter
2.28 to 1
In THW insulation
1 fit
In XHHW-2 insulation
1 fit

Before you pull 1

250 kcmil THHN in other 1-1/2" conduit

250 kcmil THHN in other Rigid sizes

Other wire sizes in 1-1/2" Rigid

Charts