ConduitCount

How many #3 THHN fit in 1-1/2" EMT?

83 AWG THHN/THWN-2 wires in 1-1/2" Electrical metallic tubing

2.036 sq in × 40 % = 0.8144 sq in allowed. ÷ 0.0973 sq in per wire = 8.37, so 8.

8 #3 THHN in 1-1/2" EMT, drawn to scale

This pull in numbers

8 wires fill
38.2 % of 1-1/2" EMT
Limit for three or more
40 %
For 9 or more
2" EMT, up to 13
Pipe to wire diameter
4.57 to 1
In THW insulation
7 fit
In XHHW-2 insulation
8 fit

Before you pull 8

#3 THHN in other 1-1/2" conduit

#3 THHN in other EMT sizes

Other wire sizes in 1-1/2" EMT

Charts