ConduitCount

How many #1/0 THHN fit in 1-1/2" EMT?

41/0 AWG THHN/THWN-2 wires in 1-1/2" Electrical metallic tubing

2.036 sq in × 40 % = 0.8144 sq in allowed. ÷ 0.1855 sq in per wire = 4.39, so 4.

4 #1/0 THHN in 1-1/2" EMT, drawn to scale

This pull in numbers

4 wires fill
36.4 % of 1-1/2" EMT
Limit for three or more
40 %
For 5 or more
2" EMT, up to 7
Pipe to wire diameter
3.31 to 1
In THW insulation
3 fit
In XHHW-2 insulation
4 fit

Before you pull 4

#1/0 THHN in other 1-1/2" conduit

#1/0 THHN in other EMT sizes

Other wire sizes in 1-1/2" EMT

Charts