How many 350 kcmil THHN fit in 2-1/2" IMC?

4350 kcmil THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.5242 sq in per wire = 3.92, which Note 7 rounds up to 4 because the decimal is 0.8 or more.

4 350 kcmil THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

4 wires fill
40.8 % of 2-1/2" IMC
Limit for three or more
40 %
For 5 or more
3" IMC, up to 6
Pipe to wire diameter
3.13 to 1
In THW insulation
3 fit
In XHHW-2 insulation
4 fit

The pipe is 3.13 times the wire's diameter, inside the 2.8 to 3.2 range where three wires can wedge side by side on a pull. If you pull exactly three, go up a size or pull with care.

Before you pull 4