ConduitCount

How many #4/0 THHN fit in 3" Rigid?

94/0 AWG THHN/THWN-2 wires in 3" Rigid metal conduit (RMC, GRC)

7.499 sq in × 40 % = 2.9996 sq in allowed. ÷ 0.3237 sq in per wire = 9.27, so 9.

9 #4/0 THHN in 3" Rigid, drawn to scale

This pull in numbers

9 wires fill
38.8 % of 3" Rigid
Limit for three or more
40 %
For 10 or more
3-1/2" Rigid, up to 12
Pipe to wire diameter
4.81 to 1
In THW insulation
8 fit
In XHHW-2 insulation
9 fit

Before you pull 9

#4/0 THHN in other 3" conduit

#4/0 THHN in other Rigid sizes

Other wire sizes in 3" Rigid

Charts