ConduitCount

How many #4 THHN fit in 1-1/2" IMC?

114 AWG THHN/THWN-2 wires in 1-1/2" Intermediate metal conduit

2.225 sq in × 40 % = 0.8900 sq in allowed. ÷ 0.0824 sq in per wire = 10.80, which Note 7 rounds up to 11 because the decimal is 0.8 or more.

11 #4 THHN in 1-1/2" IMC, drawn to scale

This pull in numbers

11 wires fill
40.7 % of 1-1/2" IMC
Limit for three or more
40 %
For 12 or more
2" IMC, up to 17
Pipe to wire diameter
5.19 to 1
In THW insulation
9 fit
In XHHW-2 insulation
11 fit

Before you pull 11

#4 THHN in other 1-1/2" conduit

#4 THHN in other IMC sizes

Other wire sizes in 1-1/2" IMC

Charts