ConduitCount

How many #6 THHN fit in 2-1/2" PVC Sch 80?

326 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 80

4.119 sq in × 40 % = 1.6476 sq in allowed. ÷ 0.0507 sq in per wire = 32.50, so 32.

32 #6 THHN in 2-1/2" PVC Sch 80, drawn to scale

This pull in numbers

32 wires fill
39.4 % of 2-1/2" PVC Sch 80
Limit for three or more
40 %
For 33 or more
3" PVC Sch 80, up to 51
Pipe to wire diameter
9.02 to 1
In THW insulation
22 fit
In XHHW-2 insulation
28 fit

Before you pull 32

#6 THHN in other 2-1/2" conduit

#6 THHN in other PVC Sch 80 sizes

Other wire sizes in 2-1/2" PVC Sch 80