ConduitCount

How many #6 THHN fit in 3" IMC?

626 AWG THHN/THWN-2 wires in 3" Intermediate metal conduit

7.922 sq in × 40 % = 3.1688 sq in allowed. ÷ 0.0507 sq in per wire = 62.50, so 62.

62 #6 THHN in 3" IMC, drawn to scale

This pull in numbers

62 wires fill
39.7 % of 3" IMC
Limit for three or more
40 %
For 63 or more
3-1/2" IMC, up to 83
Pipe to wire diameter
12.50 to 1
In THW insulation
43 fit
In XHHW-2 insulation
53 fit

Before you pull 62

#6 THHN in other 3" conduit

#6 THHN in other IMC sizes

Other wire sizes in 3" IMC

Charts