ConduitCount

How many #6 THHN fit in 4" IMC?

1076 AWG THHN/THWN-2 wires in 4" Intermediate metal conduit

13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.0507 sq in per wire = 107.54, so 107.

107 #6 THHN in 4" IMC, drawn to scale

This pull in numbers

107 wires fill
39.8 % of 4" IMC
Limit for three or more
40 %
For 108 or more
no bigger IMC
Pipe to wire diameter
16.40 to 1
In THW insulation
75 fit
In XHHW-2 insulation
92 fit

Before you pull 107

#6 THHN in other 4" conduit

#6 THHN in other IMC sizes

Other wire sizes in 4" IMC

Charts