How many #1/0 THHN fit in 3-1/2" EMT?

251/0 AWG THHN/THWN-2 wires in 3-1/2" Electrical metallic tubing

11.545 sq in × 40 % = 4.6180 sq in allowed. ÷ 0.1855 sq in per wire = 24.89, which Note 7 rounds up to 25 because the decimal is 0.8 or more.

25 #1/0 THHN in 3-1/2" EMT, drawn to scale

This pull in numbers

25 wires fill
40.2 % of 3-1/2" EMT
Limit for three or more
40 %
For 26 or more
4" EMT, up to 32
Pipe to wire diameter
7.89 to 1
In THW insulation
20 fit
In XHHW-2 insulation
25 fit

Before you pull 25

#1/0 THHN in other 3-1/2" conduit

#1/0 THHN in other EMT sizes

Other wire sizes in 3-1/2" EMT