ConduitCount

How many #1/0 THHN fit in 3-1/2" Rigid?

211/0 AWG THHN/THWN-2 wires in 3-1/2" Rigid metal conduit (RMC, GRC)

10.010 sq in × 40 % = 4.0040 sq in allowed. ÷ 0.1855 sq in per wire = 21.58, so 21.

21 #1/0 THHN in 3-1/2" Rigid, drawn to scale

This pull in numbers

21 wires fill
38.9 % of 3-1/2" Rigid
Limit for three or more
40 %
For 22 or more
4" Rigid, up to 27
Pipe to wire diameter
7.35 to 1
In THW insulation
18 fit
In XHHW-2 insulation
22 fit

Before you pull 21

#1/0 THHN in other 3-1/2" conduit

#1/0 THHN in other Rigid sizes

Other wire sizes in 3-1/2" Rigid

Charts