ConduitCount

How many #1/0 THHN fit in 4" Rigid?

271/0 AWG THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.1855 sq in per wire = 27.78, so 27.

27 #1/0 THHN in 4" Rigid, drawn to scale

This pull in numbers

27 wires fill
38.9 % of 4" Rigid
Limit for three or more
40 %
For 28 or more
5" Rigid, up to 43
Pipe to wire diameter
8.33 to 1
In THW insulation
23 fit
In XHHW-2 insulation
28 fit

Before you pull 27

#1/0 THHN in other 4" conduit

#1/0 THHN in other Rigid sizes

Other wire sizes in 4" Rigid

Charts