ConduitCount

How many #2 THHN fit in 2-1/2" IMC?

172 AWG THHN/THWN-2 wires in 2-1/2" Intermediate metal conduit

5.135 sq in × 40 % = 2.0540 sq in allowed. ÷ 0.1158 sq in per wire = 17.74, so 17.

17 #2 THHN in 2-1/2" IMC, drawn to scale

This pull in numbers

17 wires fill
38.3 % of 2-1/2" IMC
Limit for three or more
40 %
For 18 or more
3" IMC, up to 27
Pipe to wire diameter
6.66 to 1
In THW insulation
15 fit
In XHHW-2 insulation
18 fit

Before you pull 17

#2 THHN in other 2-1/2" conduit

#2 THHN in other IMC sizes

Other wire sizes in 2-1/2" IMC

Charts