ConduitCount

How many #2 THHN fit in 1-1/2" IMC?

72 AWG THHN/THWN-2 wires in 1-1/2" Intermediate metal conduit

2.225 sq in × 40 % = 0.8900 sq in allowed. ÷ 0.1158 sq in per wire = 7.69, so 7.

7 #2 THHN in 1-1/2" IMC, drawn to scale

This pull in numbers

7 wires fill
36.4 % of 1-1/2" IMC
Limit for three or more
40 %
For 8 or more
2" IMC, up to 12
Pipe to wire diameter
4.38 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 7

#2 THHN in other 1-1/2" conduit

#2 THHN in other IMC sizes

Other wire sizes in 1-1/2" IMC

Charts