ConduitCount

How many #2 THHN fit in 4" IMC?

472 AWG THHN/THWN-2 wires in 4" Intermediate metal conduit

13.631 sq in × 40 % = 5.4524 sq in allowed. ÷ 0.1158 sq in per wire = 47.08, so 47.

47 #2 THHN in 4" IMC, drawn to scale

This pull in numbers

47 wires fill
39.9 % of 4" IMC
Limit for three or more
40 %
For 48 or more
no bigger IMC
Pipe to wire diameter
10.85 to 1
In THW insulation
41 fit
In XHHW-2 insulation
47 fit

Before you pull 47

#2 THHN in other 4" conduit

#2 THHN in other IMC sizes

Other wire sizes in 4" IMC

Charts