ConduitCount

How many #2 THHN fit in 2" IMC?

122 AWG THHN/THWN-2 wires in 2" Intermediate metal conduit

3.630 sq in × 40 % = 1.4520 sq in allowed. ÷ 0.1158 sq in per wire = 12.54, so 12.

12 #2 THHN in 2" IMC, drawn to scale

This pull in numbers

12 wires fill
38.3 % of 2" IMC
Limit for three or more
40 %
For 13 or more
2-1/2" IMC, up to 17
Pipe to wire diameter
5.60 to 1