ConduitCount

How many #2 THHN fit in 3" IMC?

272 AWG THHN/THWN-2 wires in 3" Intermediate metal conduit

7.922 sq in × 40 % = 3.1688 sq in allowed. ÷ 0.1158 sq in per wire = 27.36, so 27.

27 #2 THHN in 3" IMC, drawn to scale

This pull in numbers

27 wires fill
39.5 % of 3" IMC
Limit for three or more
40 %
For 28 or more
3-1/2" IMC, up to 36
Pipe to wire diameter
8.27 to 1
In THW insulation
23 fit
In XHHW-2 insulation
27 fit

Before you pull 27

#2 THHN in other 3" conduit

#2 THHN in other IMC sizes

Other wire sizes in 3" IMC

Charts