ConduitCount

How many 250 kcmil THHN fit in 3" Rigid?

7250 kcmil THHN/THWN-2 wires in 3" Rigid metal conduit (RMC, GRC)

7.499 sq in × 40 % = 2.9996 sq in allowed. ÷ 0.3970 sq in per wire = 7.56, so 7.

7 250 kcmil THHN in 3" Rigid, drawn to scale

This pull in numbers

7 wires fill
37.1 % of 3" Rigid
Limit for three or more
40 %
For 8 or more
3-1/2" Rigid, up to 10
Pipe to wire diameter
4.35 to 1
In THW insulation
6 fit
In XHHW-2 insulation
7 fit

Before you pull 7

250 kcmil THHN in other 3" conduit

250 kcmil THHN in other Rigid sizes

Other wire sizes in 3" Rigid