ConduitCount

How many 250 kcmil THHN fit in 4" Rigid?

13250 kcmil THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.3970 sq in per wire = 12.98, which Note 7 rounds up to 13 because the decimal is 0.8 or more.

13 250 kcmil THHN in 4" Rigid, drawn to scale

This pull in numbers

13 wires fill
40.1 % of 4" Rigid
Limit for three or more
40 %
For 14 or more
5" Rigid, up to 20
Pipe to wire diameter
5.70 to 1
In THW insulation
11 fit
In XHHW-2 insulation
13 fit

Before you pull 13

250 kcmil THHN in other 4" conduit

250 kcmil THHN in other Rigid sizes

Other wire sizes in 4" Rigid

Charts