ConduitCount

How many #10 THHN fit in 2" Rigid?

6410 AWG THHN/THWN-2 wires in 2" Rigid metal conduit (RMC, GRC)

3.408 sq in × 40 % = 1.3632 sq in allowed. ÷ 0.0211 sq in per wire = 64.61, so 64.

64 #10 THHN in 2" Rigid, drawn to scale

This pull in numbers

64 wires fill
39.6 % of 2" Rigid
Limit for three or more
40 %
For 65 or more
2-1/2" Rigid, up to 92
Pipe to wire diameter
12.70 to 1
In THW insulation
56 fit
In XHHW-2 insulation
56 fit

Before you pull 64

#10 THHN in other 2" conduit

#10 THHN in other Rigid sizes

Other wire sizes in 2" Rigid

Charts