How many 250 kcmil THHN fit in 3" IMC?

8250 kcmil THHN/THWN-2 wires in 3" Intermediate metal conduit

7.922 sq in × 40 % = 3.1688 sq in allowed. ÷ 0.3970 sq in per wire = 7.98, which Note 7 rounds up to 8 because the decimal is 0.8 or more.

8 250 kcmil THHN in 3" IMC, drawn to scale

This pull in numbers

8 wires fill
40.1 % of 3" IMC
Limit for three or more
40 %
For 9 or more
3-1/2" IMC, up to 10
Pipe to wire diameter
4.47 to 1
In THW insulation
7 fit
In XHHW-2 insulation
8 fit

Before you pull 8

250 kcmil THHN in other 3" conduit

250 kcmil THHN in other IMC sizes

Other wire sizes in 3" IMC