53/0 AWG THHN/THWN-2 wires in 2" Electrical metallic tubing

3.356 sq in × 40 % = 1.3424 sq in allowed. ÷ 0.2679 sq in per wire = 5.01, so 5.

5 #3/0 THHN in 2" EMT, drawn to scale

This pull in numbers

5 wires fill
39.9 % of 2" EMT
Limit for three or more
40 %
For 6 or more
2-1/2" EMT, up to 8
Pipe to wire diameter
3.54 to 1
In THW insulation
4 fit
In XHHW-2 insulation
5 fit