ConduitCount

How many #4/0 THHN fit in 2" EMT?

44/0 AWG THHN/THWN-2 wires in 2" Electrical metallic tubing

3.356 sq in × 40 % = 1.3424 sq in allowed. ÷ 0.3237 sq in per wire = 4.15, so 4.

4 #4/0 THHN in 2" EMT, drawn to scale

This pull in numbers

4 wires fill
38.6 % of 2" EMT
Limit for three or more
40 %
For 5 or more
2-1/2" EMT, up to 7
Pipe to wire diameter
3.22 to 1
In THW insulation
3 fit
In XHHW-2 insulation
4 fit

Before you pull 4

#4/0 THHN in other 2" conduit

#4/0 THHN in other EMT sizes

Other wire sizes in 2" EMT

Charts