ConduitCount

How many #3/0 THHN fit in 2-1/2" PVC Sch 80?

63/0 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 80

4.119 sq in × 40 % = 1.6476 sq in allowed. ÷ 0.2679 sq in per wire = 6.15, so 6.

6 #3/0 THHN in 2-1/2" PVC Sch 80, drawn to scale

This pull in numbers

6 wires fill
39.0 % of 2-1/2" PVC Sch 80
Limit for three or more
40 %
For 7 or more
3" PVC Sch 80, up to 9
Pipe to wire diameter
3.92 to 1
In THW insulation
5 fit
In XHHW-2 insulation
6 fit

Before you pull 6

#3/0 THHN in other 2-1/2" conduit

#3/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 2-1/2" PVC Sch 80

Charts