How many #1 THHN fit in 3-1/2" EMT?
291 AWG THHN/THWN-2 wires in 3-1/2" Electrical metallic tubing
11.545 sq in × 40 % = 4.6180 sq in allowed. ÷ 0.1562 sq in per wire = 29.56, so 29.
This pull in numbers
- 29 wires fill
- 39.2 % of 3-1/2" EMT
- Limit for three or more
- 40 %
- For 30 or more
- 4" EMT, up to 37
- Pipe to wire diameter
- 8.60 to 1
- In THW insulation
- 24 fit
- In XHHW-2 insulation
- 30 fit
Before you pull 29
- The ground counts. Every wire in the pipe counts toward fill, the green or bare ground and the neutrals too. 29 is the total, not the hots.
- Derating. If all 29 were current-carrying, each would be adjusted to 45 % of its ampacity (Table 310.15(C)(1)): a #1 THHN at 145 A in the 90 °C column becomes 65.3 A. Grounds don't count as current-carrying. How derating works
- Bends. A full pipe pulls hard. Keep to 360° of bends between pull points, less for a tight fill.
#1 THHN in other 3-1/2" conduit
| Conduit | Inside area | Most #1 THHN |
|---|---|---|
| Electrical metallic tubing | 11.545 | 29 |
| Intermediate metal conduit | 10.584 | 27 |
| Rigid metal conduit (RMC, GRC) | 10.010 | 25 |
| Rigid PVC conduit, Schedule 40 | 9.737 | 25 |
| Rigid PVC conduit, Schedule 80 | 8.688 | 22 |
| Flexible metal conduit (FMC, Greenfield) | 9.621 | 24 |
| Liquidtight flexible metal conduit (LFMC) | 9.731 | 25 |
#1 THHN in other EMT sizes
Other wire sizes in 3-1/2" EMT
#8: 126#6: 91#4: 56#3: 47#2: 40#1: 29#1/0: 25#2/0: 20#3/0: 17#4/0: 14250 kcmil: 11300 kcmil: 10350 kcmil: 9500 kcmil: 6