ConduitCount

How many 300 kcmil THHN fit in 3-1/2" IMC?

9300 kcmil THHN/THWN-2 wires in 3-1/2" Intermediate metal conduit

10.584 sq in × 40 % = 4.2336 sq in allowed. ÷ 0.4608 sq in per wire = 9.19, so 9.

9 300 kcmil THHN in 3-1/2" IMC, drawn to scale

This pull in numbers

9 wires fill
39.2 % of 3-1/2" IMC
Limit for three or more
40 %
For 10 or more
4" IMC, up to 12
Pipe to wire diameter
4.79 to 1
In THW insulation
8 fit
In XHHW-2 insulation
9 fit

Before you pull 9

300 kcmil THHN in other 3-1/2" conduit

300 kcmil THHN in other IMC sizes

Other wire sizes in 3-1/2" IMC