ConduitCount

How many #4/0 THHN fit in 3-1/2" EMT?

144/0 AWG THHN/THWN-2 wires in 3-1/2" Electrical metallic tubing

11.545 sq in × 40 % = 4.6180 sq in allowed. ÷ 0.3237 sq in per wire = 14.27, so 14.

14 #4/0 THHN in 3-1/2" EMT, drawn to scale

This pull in numbers

14 wires fill
39.3 % of 3-1/2" EMT
Limit for three or more
40 %
For 15 or more
4" EMT, up to 18
Pipe to wire diameter
5.97 to 1
In THW insulation
12 fit
In XHHW-2 insulation
14 fit

Before you pull 14

#4/0 THHN in other 3-1/2" conduit

#4/0 THHN in other EMT sizes

Other wire sizes in 3-1/2" EMT

Charts