How many 300 kcmil THHN fit in 3-1/2" PVC Sch 40?

8300 kcmil THHN/THWN-2 wires in 3-1/2" Rigid PVC conduit, Schedule 40

9.737 sq in × 40 % = 3.8948 sq in allowed. ÷ 0.4608 sq in per wire = 8.45, so 8.

8 300 kcmil THHN in 3-1/2" PVC Sch 40, drawn to scale

This pull in numbers

8 wires fill
37.9 % of 3-1/2" PVC Sch 40
Limit for three or more
40 %
For 9 or more
4" PVC Sch 40, up to 11
Pipe to wire diameter
4.60 to 1
In THW insulation
7 fit
In XHHW-2 insulation
8 fit

Before you pull 8

300 kcmil THHN in other 3-1/2" conduit

300 kcmil THHN in other PVC Sch 40 sizes

Other wire sizes in 3-1/2" PVC Sch 40

Charts