ConduitCount

How many #4/0 THHN fit in 4" Rigid?

164/0 AWG THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.3237 sq in per wire = 15.92, which Note 7 rounds up to 16 because the decimal is 0.8 or more.

16 #4/0 THHN in 4" Rigid, drawn to scale

This pull in numbers

16 wires fill
40.2 % of 4" Rigid
Limit for three or more
40 %
For 17 or more
5" Rigid, up to 25
Pipe to wire diameter
6.31 to 1
In THW insulation
14 fit
In XHHW-2 insulation
16 fit

Before you pull 16

#4/0 THHN in other 4" conduit

#4/0 THHN in other Rigid sizes

Other wire sizes in 4" Rigid

Charts