ConduitCount

How many #2 THHN fit in 4" PVC Sch 80?

392 AWG THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 80

11.258 sq in × 40 % = 4.5032 sq in allowed. ÷ 0.1158 sq in per wire = 38.89, which Note 7 rounds up to 39 because the decimal is 0.8 or more.

39 #2 THHN in 4" PVC Sch 80, drawn to scale

This pull in numbers

39 wires fill
40.1 % of 4" PVC Sch 80
Limit for three or more
40 %
For 40 or more
5" PVC Sch 80, up to 61
Pipe to wire diameter
9.86 to 1
In THW insulation
33 fit
In XHHW-2 insulation
39 fit

Before you pull 39

#2 THHN in other 4" conduit

#2 THHN in other PVC Sch 80 sizes

Other wire sizes in 4" PVC Sch 80

Charts