896 AWG THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 80

11.258 sq in × 40 % = 4.5032 sq in allowed. ÷ 0.0507 sq in per wire = 88.82, which Note 7 rounds up to 89 because the decimal is 0.8 or more.

89 #6 THHN in 4" PVC Sch 80, drawn to scale

This pull in numbers

89 wires fill
40.1 % of 4" PVC Sch 80
Limit for three or more
40 %
For 90 or more
5" PVC Sch 80, up to 141
Pipe to wire diameter
14.91 to 1
In THW insulation
62 fit
In XHHW-2 insulation
76 fit