241/0 AWG THHN/THWN-2 wires in 4" Rigid PVC conduit, Schedule 80

11.258 sq in × 40 % = 4.5032 sq in allowed. ÷ 0.1855 sq in per wire = 24.28, so 24.

24 #1/0 THHN in 4" PVC Sch 80, drawn to scale

This pull in numbers

24 wires fill
39.5 % of 4" PVC Sch 80
Limit for three or more
40 %
For 25 or more
5" PVC Sch 80, up to 38
Pipe to wire diameter
7.79 to 1
In THW insulation
20 fit
In XHHW-2 insulation
24 fit