ConduitCount

How many #6 THHN fit in 4" Rigid?

1016 AWG THHN/THWN-2 wires in 4" Rigid metal conduit (RMC, GRC)

12.882 sq in × 40 % = 5.1528 sq in allowed. ÷ 0.0507 sq in per wire = 101.63, so 101.

101 #6 THHN in 4" Rigid, drawn to scale

This pull in numbers

101 wires fill
39.8 % of 4" Rigid
Limit for three or more
40 %
For 102 or more
5" Rigid, up to 159
Pipe to wire diameter
15.94 to 1
In THW insulation
71 fit
In XHHW-2 insulation
87 fit

Before you pull 101

#6 THHN in other 4" conduit

#6 THHN in other Rigid sizes

Other wire sizes in 4" Rigid

Charts