ConduitCount

How many #1/0 THHN fit in 2-1/2" PVC Sch 80?

91/0 AWG THHN/THWN-2 wires in 2-1/2" Rigid PVC conduit, Schedule 80

4.119 sq in × 40 % = 1.6476 sq in allowed. ÷ 0.1855 sq in per wire = 8.88, which Note 7 rounds up to 9 because the decimal is 0.8 or more.

9 #1/0 THHN in 2-1/2" PVC Sch 80, drawn to scale

This pull in numbers

9 wires fill
40.5 % of 2-1/2" PVC Sch 80
Limit for three or more
40 %
For 10 or more
3" PVC Sch 80, up to 14
Pipe to wire diameter
4.71 to 1
In THW insulation
7 fit
In XHHW-2 insulation
9 fit

Before you pull 9

#1/0 THHN in other 2-1/2" conduit

#1/0 THHN in other PVC Sch 80 sizes

Other wire sizes in 2-1/2" PVC Sch 80

Charts